SIMOVAC non-arc-resistant and SIMOVAC-AR arc-resistant motor controllers

-
Rated short-time withstand current up to 63 kA
-
Enclosed continuous ampere rating 400 A or 720 A
-
Lightning impulse (BIL) up to 60 kV
Air-insulated, medium-voltage, non-arc-resistant SIMOVAC and arc-resistant SIMOVAC-AR motor controllers
Siemens has provided medium-voltage controllers to users in the U.S., Canada, and around the world for construction, industrial, and utility projects for over 50 years.
The Siemens SIMOVACTM medium-voltage non-arc-resistant and SIMOVAC-ARTM arc-resistant controllers have a modular design incorporating up to two 12SVC400 (400 A) controllers, housed in a freestanding sheet steel enclosure. Each controller is UL 347 class E2, equipped with three current-limiting fuses, a non-load-break isolating switch, and a fixed-mounted vacuum contactor (plug-in type optional for 12SVC400). The enclosure is designed for front access, allowing the equipment to be located with the rear of the equipment close to a non-combustible wall.
Typical motor and feeder applications:
- Squirrel-cage induction motors (non-reversing, reversing, multi-speed or soft start)
- Transformer feeder
- Power bus feeders (tie).
Typical controller types:
- Full-voltage non-reversing (FVNR)
- Full-voltage reversing (FVR)
- Two-speed two winding (2S2W)
- Two-speed one winding (2S1W)
- Reduced-voltage autotransformer (RVAT)
- Solid-state reduced-voltage (or soft start) starter (SSRVS).
Watch the videos below to learn more about SIMOVAC and SIMOVAC-AR controllers, their Sm@rtGear option, and Shelter-Clad+ type enclosures.
Air-insulated, medium-voltage, non-arc-resistant SIMOVAC and arc-resistant SIMOVAC-AR motor controllers
Features
Features include:
- SIMOVAC-AR tested for arc-resistance to IEEE C37.20.7, type 2B
- Complies with UL 347 6th edition (same as CSA C22.2 No. 253-09) (UL / cUL Listing not available on 720 A SSRVS controller)
- 400 A bolt-in or stab-in (optional) or 720 A bolt-in vacuum contactor
- 400 A or 720 A non-load-break isolation switch
- 2.4 kV, 4.16 kV and 6.9 kV (up to 7.65 kV) system voltage ratings
- 1,200 A, 2,000 A, 3,000 A or 4,000 A main bus with standard epoxy insulation on bus bars, and with optional boots for insulating joints
- Tin- or silver-plated bus available
- Front accessible
- Main bus and ground bus are supported and braced to 63 kA two-second short-time capability
- Top-mounted pressure relief channel shipped installed for reduced site installation time
- Isolation switch with visible indication through viewing window to verify that the power cell is isolated from line-side source ‒ no need to open panel door
- Isolation switch mechanically interlocked with the access door to prevent user access to primary compartment when isolation switch is closed
- Low-voltage compartment is isolated from the medium-voltage compartment
- All components are front accessible, facilitating routine inspection or parts replacement
- Current-limiting fuses, contactor assembly and isolating switch assembly are easily removed from the enclosure
- The main bus compartment is top, side and front accessible for easy installation and extension.
Medium-voltage motor controllers are available as:
- Type 1 non-gasketed
- Type 1 gasketed (rear panels only)
- Type 2 drip resistant (SIMOVAC non-arc-resistant only)
- Type 3R (SIMOVAC non-arc-resistant only)
- Type 12 dust tight (SIMOVAC non-arc-resistant only).
Sm@rtgear technology option
Intelligent devices (circuit breakers, relays, meters, etc.) have existed for more than 30 years. These devices are self-monitoring, configurable, and communicating, but individually they are only islands of intelligence. Historically integrated remote monitoring, configuration, and control have only been available with the inclusion of upstream PMCS, PCS, DCS, or SCADA systems.
With the advent of Siemens Sma@rtGear technology, remote monitoring, configuration, and control are standard features that are integral to the electrical apparatus product.
Advantages at a glance:
- Keeping business operational with maximum uptime
- Reliable energy-efficient products and systems
- Ease of operation and maintenance
- Remote access for arc-flash mitigation
- Integration with existing equipment
- One supplier for all power distribution needs
- Long-term partner over entire lifecycle
- Technology leader with durable solutions
- 24/7 hotline support.
Sm@rtGear features, benefits and details for medium-voltage controllers:
- Types: 12SVC400, 12SVC800 contactors
- Maintenance mode: Yes
- Metering: Q200, Q100, P855
- Protective relays: Yes, standard Siemens SIPROTEC
- Remote racking: No
- Remote open/close: Yes
- HMI size: 22"
- Auto-throwover: Yes
- Temperature sensing: Yes
- Optional accessories: High-resistance grounding, partial-discharge monitoring.
For more information about the entire Sm@rtGear portfolio for low- and medium-voltage power distribution equipment, please go to Sm@rtGear™ power distribution solution.
Ratings
Footnotes:
- All main bus ratings are on a self-cooled, ventilated basis.
- Short-time duration for controllers without main bus is limited to contactor capability (with fuses).
- Insulation level is for the controller, with inductive transformers disconnected for testing (per UL 347).
- 50 kA with certain contactor/fuse combinations.
- Type 12 up to 2,000 A. Type 3R up to 3,000 A.
Footnotes:
- Refer to Controller maximum current capability table for further detail.
- Based on self-cooled transformer rating.
- With 24R fuse, interrupting capacity is 50 kA.
- With 48X or 57X fuse, interrupting capacity is 50 kA.
- Maximum fuse is 18R.
- Fuse shown will not permit transformer forced-cooling rating of 133 percent of self-cooled rating.
- For horsepower greater than 1,500, please consult factory.
- For horsepower greater than 2,500, please consult factory.
TechTopics is a series of papers that discuss issues of interest to users or specifiers of electrical equipment.
- No. 13 - Use of latched contactors to switch transformers
- No. 15 - Expected life of electrical equipment
- No. 16 - Bus joint fundamentals
- No. 17 - Main bus continuous current rating
- No. 18 - Bus joint and primary disconnect plating
- No. 19 - Bus joint current density
- No. 20 - Power factor correction capacitor - sizing for motors
- No. 26 - Ground bus ratings
- No. 33 - Clearance requirements in switchgear and control equipment
- No. 42 - Circuit breakers or vacuum contactors - application considerations
- No. 45 - Accuracy of current transformers (CTs) used in medium-voltage control equipment
- No. 46 - Selection of current transformer (CT) ratio in medium-voltage control
- No. 47 - 7.2 kV equipment basic insulation levels (BIL)
- No. 57 - Arc-flash hazard labels
- No. 58 - What is the difference between E-rated and R-rated current-limiting fuses?
- No. 70 - Arc-resistant switchgear accessibility types
- No. 79 - Working space required around electrical equipment
- No. 81 - Arc-flash incident energy mitigation
- No. 82 - Continuous current capability in ambient temperatures other than 40 °C
- No. 84 - Space heater - sizing and application principles
- No. 85 - Temperature limitations for user’s power cables
- No. 86 - Use of unshielded cables for connections in medium-voltage switchgear and motor controllers
- No. 88 - Application of maintenance grounds in switchgear
- No. 89 - Venting of exhaust gases from arc-resistant equipment
- No. 90 - Temperature ratings for external cables
- No. 92 - Heat generation estimation for SIMOVAC non-arc-resistant and SIMOVAC-AR arc-resistant medium-voltage controllers
- No. 100 - Third-party listing - UL, C-UL and CSA
- No. 102 - Tapered bus
- No. 103 - Medium-voltage controllers - fixed-mounted contactors compared to drawout contactors
- No. 104 - Arc-resistant equipment - sealing requirements
- No. 105 - Fuses and overload protection for motor starting with class E2 controllers
- No. 106 - Arc-resistant equipment - exit of exhaust plenum from buildings
- No. 108 - Lightning-impulse (BIL) ratings for medium-voltage controllers
- No. 110 - Corrosion prevention effects on electrical equipment life
- No. 112 - Use of R-rated fuses in lieu of E-rated fuses for transformers
- No. 114 - Low-ratio current transformers in medium-voltage controllers
- No. 115 - Third-party listing/labeling and recognition
- No. 116 - Arc-resistant switchgear ‒ accessibility type C
- No. 118 - Bolted construction vs. welded construction
- No. 119 - Momentary ratings – peak or rms?
- No. 120 - High-potential testing – current doesn’t matter!
- No. 122 - Current transformer thermal-rating factor
- No. 125 - Do not connect surge arresters or capacitors on the load side of solid-state, reduced-voltage (SSRVS) controllers
- No. 126 - Testing of vacuum interrupters with dc test sets
- No. 133 - Motor starting: autotransformer or soft starter?
- Entire TechTopics catalog
SIMOVAC-AR arc-resistant motor controller
The type SIMOVAC-AR equipment is classified as arc-resistant, as defined in ANSI/IEEE C37.20.7, and has been qualified in tests to carry a type 2B accessibility rating. These arc-resistant features provide an additional degree of protection to personnel in close proximity to the equipment in the event of an internal arcing fault while the equipment is operating under normal conditions. The enclosure withstands the pressures and elevated temperatures of an internal arcing fault and directs the hot gases and arc by-products into the top-mounted pressure relief channel (PRC). These arc by-products are then vented to the outside environment through an exhaust duct or plenum system. The exhaust plenum (duct) must be routed to an area where personnel will not be present when the equipment is energized.
The exhaust plenum (or duct) is provided separately, in modular shipping lengths (normally 36” (914 mm) long), and the shipping lengths are easily installed and connected together at the site.
In cases where a transition section is used to close couple SIMOVAC-AR controllers to Siemens type GM-SG-AR medium-voltage switchgear, the hot gases and burning particulates are directly exhausted into a common PRC for both SIMOVAC-AR controllers and GM-SG-AR switchgear, before being vented to the outside through a common exhaust plenum. One of the images to the right presents an exhaust plenum for a SIMOVAC-AR lineup and for a SIMOVAC-AR section connected to type GM-SG-AR switchgear section with a transition section. This figure depicts the exhaust plenum connected to the front, but the plenum may be connected to either side or to the rear, or to the top of the PRC.
Enclosures used to couple type SIMOVAC-AR controllers to other equipment (for example, transition sections, transformer throats, bus ducts, etc.) as well as specialized vertical sections within a lineup of type SIMOVAC-AR equipment that have not been qualified for resistance to internal arcing are not considered to be arc-resistant.
Reduced-voltage autotransformer controller
Reduced-voltage, autotransformer, non-reversing controller in addition to Siemens solid- state, reduced-voltage (SSRV) controller consists of a main vacuum contactor, run vacuum contactor, starting vacuum contactor, and an autotransformer.
This traditional electro-mechanical approach to starting medium-voltage motors is rated for NEMA medium-duty applications. The simplified reduced-voltage starting method has been used for years and is highly familiar to users.
Motor data must be provided when ordering to ensure that the autotransformer is sized properly.
Benefits of RVAT starting:
- Reduced torque shock damage on motor and driven load
- Increased motor and drive train reliability
- 50%, 65%, and 80% tap settings allow for flexible starting characteristics
- Easy to maintain
- Reduced hydraulic/mechanical problems
- Low-current starting limitations
- Increase starting torque
- Mechanical interlock between Run and Start contactor and between main and auxiliary high-voltage doors
- More experienced maintenance personnel available.
Starting characteristics
The various taps on the autotransformer provide the option for different starting voltages. Higher voltage taps are used for applications that require high-starting torque, or to limit the accelerating period within the duty-cycle rating of the autotransformer. Controllers are normally set to the 65-percent voltage tap when they leave the factory.
Starting-duty cycle
The autotransformers used in Siemens RVAT motor controllers are three coils and conform to UL 347 6th edition for medium duty and are suitable for general motor starting service.
The starting duty cycle rating based on a temperature rise of 115 ºC, 65% tap, with tap current 300% of motor full-load current and a power factor of 50% or less is as follows in the table below.
Solid-state reduced-voltage controller
Solid-state reduced-voltage starter (SSRVS) controller consists of a main contactor, a silicon controller rectifier (SCR) chassis and a bypass contactor (rated for full-voltage starting). Siemens SSRV complies with UL 347 6th edition.
The SSRVS controller provides the most flexible starting options, offering selectable current or voltage ramps. For emergency full-voltage starting, the bypass contactor can be used as an across-the-line starter by changing a control switch position.
As an option, the starter can be equipped with a permanent emergency across-the-line starting option including an additional set of current transformers (CTs), normal/emergency selector switch and a bimetallic overload relay. Repositioning power cables for this option is not required.
Benefits of SSRV starting:
- Reduced torque shock damage on motor and driven load
- Increased motor and drive train reliability
- Starting kVA limitation
- Maintains future system flexibility
- Soft-start and soft-stop (for pumps) to control water hammer
- Reduced hydraulic/mechanical problems.
SCR logic control
The SCR logic control incorporates the following standard protection, metering and parameter adjustments:
- Initial voltage (0 to 50 percent nominal voltage; 0 to 80 percent using extended setting)
- Current limit (100 to 400 percent of motor FLA standard; 100 to 700 percent using extended setting). Please contact Siemens representative for setting below 300 percent
- Overcurrent rating (400 percent - 30 seconds)
- Acceleration time (1 to 30 seconds standard; 1 to 90 seconds using extended setting)
- Deceleration time (0 to 30 seconds; 0 to 90 seconds using extended setting)
- Decel-final torque (0 to 10 percent sensitivity)
- Pump control - in addition to the standard start curve and torque curve, there are three selectable pump control curves and stop curves
- Pulse (kick) start (for pulse time less than 1 second, 70 to 700 percent of full-load amperes (FLA); for pulse time greater than 1 to 10 seconds, 70 to 400 percent of FLA)
- Undervoltage trip (50 to 90 percent, adjustable trip delay)
- Overvoltage trip (110 to 125 percent, adjustable trip delay 1 to 10 seconds)
- Undercurrent (load-loss) trip (0 percent equals off, 20 to 90 percent of motor FLA with adjustable trip delay adjustable from 1 to 40 seconds)
- Allowable restarts (0 to 10, adjustable time inhibit)
- Electronic overload (inverse time, two-stage programmable class 5 to 30); choose from either IEC or NEMA overload curves
- Electronic shear pin (100 to 850 percent of motor FLA with adjustable trip delay of 0 to 5 seconds)
- Phase loss (one or more phases missing with phase loss auto-reset feature)
- Shorted SCR (internal fault detected, operational after the start signal is initiated)
- Wrong connection (internal fault/motor connection, operational after the start signal is initiated)
- Starter over temperature (heat sink over temperature). Thermal sensors mounted on the heat sinks. Trips the starter when heat sink temperature rises above 185 °F (85 °C)
- Elapsed time meter, displays the motor total run time
- Time since last start
- Last start maximum current
- Starting time for last start
- Total number of starts
- Cause of last start
- Percentage of current at last trip
- Total number of trips
- RS 485 with Modbus remote terminal unit protocol (optional Profibus DO available)
- Opto-isolated inputs
- Number of relay outputs (3 form C)
- Analog output (programmable as 0-10 Vdc, or 4-20 mA, or 0-20 mA)
- Display (alphanumeric liquid-crystal display (LCD) - 2 lines x 16 characters)
- Non-volatile memory for programming and faults
- Programmable in four languages
- Residual ground-fault protection.
Load-interrupter switch (LIS)
The photo to the right shows the manually operated, single-throw, gang-operated load-interrupter switch available in types SIMOVAC and SIMOVAC-AR assemblies, rated either 600 A or 1,200 A. Quick-make, quick-break arcing blades combined with arc chutes provides positive, three-phase interruption of load currents. The switch uses a quick make/quick break stored-energy operator. The load-interrupter switch may be unfused or equipped with current-limiting fuses to provide short-circuit current interrupting capacity. Fuses are mounted below the switch. The table below shows the ratings for the load-interrupter switch.
The door and switch operating handle are mechanically interlocked to ensure the door cannot be opened with the switch closed and the switch cannot be closed with the door open. In addition, the switch is covered with a Lexan barrier. The switches are fixed mounted and can be equipped with fixed-mounted fuses. 600 A load-interrupter switches, whether fused or non-fused, fit in a full height 36” (914 mm) wide section.
1,200 A load-interrupter switches, whether fused or non-fused, require a full-height 48” (1,218 mm) wide section.
Optional accessories for the load-interrupter switches include auxiliary contacts (2 NO and 2 NC) or blown fuse indicator.

Improving electrical safety by design
Learn about how our products, solutions, and services can help address various challenges at your facility.